48

1.8V supply low

Danfoss · VLT HVAC Drive High Power

What does 48 mean?

The 1.8V DC supply on the control card, crucial for its internal logic, has dropped below its allowable limits. This low voltage indicates a potential fault on the control card itself or an overload caused by an option card, leading to unstable operation or complete control card failure.

Complete Troubleshooting Guide

  1. 1

    Check for a defective control card that may be failing to regulate its internal 1.8V supply.

  2. 2

    If an option card is present, check for overvoltage or excessive current draw from the option card, which might be loading down the 1.8V supply.

  3. 3

    Try removing the option card temporarily to see if the warning clears.