49

Speed limit exceeded

Danfoss · VLT HVAC Drive High Power

What does 49 mean?

The motor's actual speed is outside the range defined by parameter 4-11 (Motor Speed Low Limit [RPM]) and parameter 4-13 (Motor Speed High Limit [RPM]). If the speed drops below parameter 1-86 (Trip Speed Low [RPM]) (excluding start/stop conditions), the frequency converter will trip, indicating a potential control issue or an abnormal operating condition.

Complete Troubleshooting Guide

  1. 1

    Review and adjust parameters 4-11 (Motor Speed Low Limit [RPM]) and 4-13 (Motor Speed High Limit [RPM]) to match the application's required speed range.

  2. 2

    Verify that the motor's operating speed is consistent with the commanded speed.

  3. 3

    Check for mechanical issues on the motor or load that could cause speed deviations.

  4. 4

    Adjust parameter 1-86 (Trip Speed Low [RPM]) if the low speed trip is unwanted for certain operating states.