ALARM 12
Torque limit
Danfoss · VLT HVAC Drive High Power
What does ALARM 12 mean?
The motor's torque has exceeded the value set in parameter 4-16 Torque Limit Motor Mode or the generator torque limit in parameter 4-17 Torque Limit Generator Mode. This condition can be a warning or escalate to an alarm and trip, protecting the mechanical system from excessive stress.
Complete Troubleshooting Guide
- 1
If the motor torque limit is exceeded during ramp-up, extend the ramp-up time.
- 2
If the generator torque limit is exceeded during ramp-down, extend the ramp-down time.
- 3
If the torque limit occurs during steady-state operation, increase the torque limit, but ensure the mechanical system can safely operate at the higher torque.
- 4
Check the application for any excessive current draw on the motor.