ALARM 2

Live zero error

Danfoss · VLT HVAC Drive High Power

What does ALARM 2 mean?

The signal on one of the analog inputs is less than 50% of the programmed minimum value. This condition, appearing if parameter 6-01 Live Zero Timeout Function is programmed, often indicates broken wiring or a faulty sensor/device sending the analog signal, risking incorrect operation or control.

Complete Troubleshooting Guide

  1. 1

    Check connections on all analog input terminals (control card 53/54 with 55 common, MCB 101 terminals 11/12 with 10 common, MCB 109 terminals 1/3/5 with 2/4/6 common).

  2. 2

    Verify that the frequency converter's programming and switch settings correctly match the type of analog signal being used.

  3. 3

    Perform an input terminal signal test to confirm proper signal reception.