1
10 Volts low
Danfoss · VLT HVAC-FC 102 Frequency Converter
What does 1 mean?
The control card voltage from terminal 50 has dropped below 10 V. This is typically caused by an overloaded 10 V supply (exceeding 15 mA or below 590 Ω minimum resistance) or a short circuit in a connected potentiometer or its wiring. If left unresolved, this can lead to unstable control card operation or system shutdown.
Additional Steps
Steps 1–2 are listed in Priority Fix.
- 3
If the warning persists even after external wiring is removed, the control card itself is likely defective and requires replacement.
Source: Danfoss VLT HVAC-FC 102 Frequency Converter
View Official PDF