12
Torque limit
Danfoss · VLT HVAC-FC 102 Frequency Converter
What does 12 mean?
The motor torque has exceeded the programmed limits in parameter 4-16 (Motor Mode) or 4-17 (Generator Mode). This can be caused by excessive load, rapid acceleration/deceleration, or incorrect limit settings. Persistent torque limiting can hinder application performance or cause unexpected stops.
Complete Troubleshooting Guide
- 1
If the motor torque limit is exceeded during ramp up or generator torque limit during ramp down, extend the respective ramp time.
- 2
If the torque limit occurs while running, cautiously increase the torque limit (e.g., 4-16, 4-17), ensuring the system can operate safely at a higher torque.
- 3
Check the application for any excessive current draw on the motor or mechanical binding that could cause high torque.