Live zero error
Danfoss · VLT HVAC-FC 102 Frequency Converter
What does 2 mean?
This warning or alarm appears if programmed in 6-01 Live Zero Timeout Function. It indicates that the signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. Common causes include broken wiring or a faulty device sending the signal, which can lead to incorrect process control.
Complete Troubleshooting Guide
- 1
Check connections on all analog input terminals (control card terminals 53, 54, 55, MCB 101 terminals 11, 12, 10, MCB 109 terminals 1, 3, 5, 2, 4, 6).
- 2
Verify that the frequency converter programming and switch settings correctly match the analog signal type being used.
- 3
Perform the Input Terminal Signal Test available in the drive to diagnose the specific input issue.