68

Safe Stop activated

Danfoss · VLT HVAC-FC 102 Frequency Converter

What does 68 mean?

The Safe Stop function has been activated, bringing the motor to a controlled stop and preventing unintended restart. This is a critical safety feature typically triggered by an external safety input. The drive will remain in this state until the safety input is cleared and a reset commanded.

Complete Troubleshooting Guide

  1. 1

    Verify that the external safety system that triggered Safe Stop has been reset and its associated safety conditions are cleared.

  2. 2

    Apply 24 V DC to terminal 37, which is the designated Safe Stop input, to de-activate the safety function.

  3. 3

    Send a reset signal to the frequency converter via the control panel reset key, digital I/O, or fieldbus to restart normal operation.