Übersetzen...
CJChxx.Fault

Cold Junction Data Fault (5069-IY4, 5069-IY4K)

Allen-Bradley · Compact 5000 I/O Analog Modules

Was bedeutet CJChxx.Fault ?

This boolean tag indicates that the cold junction data for a specific channel (xx) is inaccurate and cannot be trusted for application use. A value of 1 signifies bad data, causing a fault. The tag automatically resets to 0 once the underlying condition is resolved.

Häufige Ursachen

  • Cold junction channel (CJChxx) is disabled
  • Open Wire condition at the cold junction
  • Underrange/Overrange condition for the cold junction temperature
  • Short Circuit condition at the cold junction sensor or wiring

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the channel (CJChxx) is enabled in the module configuration.

  2. 2

    Check for an Open Wire condition at the cold junction sensor or wiring.

  3. 3

    Measure the cold junction temperature to ensure it is within the specified operating range (not underrange or overrange).

  4. 4

    Inspect the cold junction sensor and wiring for any short circuits.

Alle Codes in diesem Handbuch durchsuchen (33)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Allen-Bradley Compact 5000 I/O Analog Modules