CJChxx.OpenWire

Cold Junction Open Wire (5069-IY4, 5069-IY4K)

Allen-Bradley · Compact 5000 I/O Analog Modules

Was bedeutet CJChxx.OpenWire ?

This boolean tag indicates that the cold junction wire is disconnected from channel (xx) or the Removable Terminal Block (RTB) is removed from the module. A value of 1 signifies an open wire condition. This prevents accurate cold junction temperature readings.

Häufige Ursachen

  • Cold junction signal wire disconnected from channel (CJChxx) terminals
  • Removable Terminal Block (RTB) removed from the module

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Confirm that the cold junction signal wire is securely connected to the designated terminals of channel (CJChxx).

  2. 2

    Verify that one of the compatible RTBs (5069-RTB14CJC-SPRING or 5069-RTB14CJC-SCREW) is correctly installed on the module.