ModuleStatus:FlashingRed

Recoverable Module Fault or Connection Timeout

Allen-Bradley · Compact 5000 I/O Analog Modules

Was bedeutet ModuleStatus:FlashingRed ?

The Module Status indicator is flashing red, which can signify several conditions: a module firmware update is in progress or failed, the device has experienced a recoverable fault, or a connection to the module has timed out. The specific cause needs to be determined via software diagnostics.

Häufige Ursachen

  • Module firmware update is in progress
  • Module firmware update attempt failed
  • Device experienced a recoverable internal fault
  • Connection to the module has timed out (e.g., due to cable failure)

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Allow any module firmware update to progress to completion.

  2. 2

    If a firmware update failed, re-attempt the firmware update procedure.

  3. 3

    Use the Logix Designer application to access the module's configuration (Connection and Module Info categories) to determine the specific fault type.

  4. 4

    To clear a recoverable fault, cycle power to the module (power off, then on).

  5. 5

    To clear a recoverable fault, click 'Reset Module' in the Logix Designer application via the Module Info category of the Module Properties dialog box.

  6. 6

    Use the Logix Designer application to check the Connection category in Module Properties for connection timeout status and determine the cause (e.g., inspect Ethernet cable integrity).