Übersetzen...
FB ENVELOPE Value 2

Overflow (InValue above the envelope)

Beckhoff · TwinSAFE Logic FB

Was bedeutet FB ENVELOPE Value 2 ?

The input value (InValue) has exceeded the defined upper limit of the envelope in the FB Envelope function block. This indicates a deviation from the expected operating range, potentially causing the safety function to trip or behave unpredictably, leading to an unsafe state.

Häufige Ursachen

  • Analog sensor (e.g., pressure, flow, temperature) reading above its expected operating range due to calibration drift or process upset.
  • Incorrect upper limit parameter (e.g., P1-06) set too low within the FB Envelope function block configuration.
  • Signal conditioning error causing the input value to be amplified above the envelope's upper threshold (e.g., faulty amplifier).
  • Sensor failure mode where the output is stuck at its maximum value or an open circuit on a voltage input (e.g., 10V pull-up).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Measure the actual process variable (PV) and compare it to the 'InValue' displayed in the safety logic.

  2. 2

    2. Verify the analog sensor's output (e.g., 4-20mA, 0-10V) directly at the input terminals of the safety module (e.g., EL3xxx terminal X2).

  3. 3

    3. Check the 'Upper Limit' parameter (e.g., P1-06) within the FB Envelope configuration for correct scaling and value.

  4. 4

    4. Calibrate the associated analog sensor according to manufacturer specifications.

  5. 5

    5. Inspect the signal wiring from the sensor to the safety module for damage or short circuits to an external voltage source.

Alle Codes in diesem Handbuch durchsuchen (60)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes