Monitoring Discrepancy Error - Input Group 1
Beckhoff · TwinSAFE Logic FB
Was bedeutet FB MON Bit 0 ?
A discrepancy has been detected between the channels of input group 1 in the FB MON function block. This means the redundant inputs are not switching in sync or are reporting different states, indicating a potential sensor fault, wiring issue, or incorrect timing that could compromise the monitoring function, leading to a safety stop.
Häufige Ursachen
- One channel of a monitored redundant safety input device (e.g., safety gate switch S1-S2) is stuck open or closed.
- Broken conductor or loose terminal connection on one channel (e.g., input MonIn_CH1) of the monitored safety device.
- Asynchronous switching of the redundant contacts within a safety device due to mechanical wear or sticky contacts.
- Electrical noise or transient voltage spikes on one input channel causing a momentary discrepancy.
- Input synchronization time parameter (e.g., P_MON_DISC_TIME_G1) set too short for the specific safety device's characteristics.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Actuate the monitored safety device (e.g., open/close safety gate) and observe the corresponding input LEDs (e.g., IN_G1_A, IN_G1_B) on the safety controller for synchronized state changes.
- 2
Measure continuity across both redundant output contacts of the safety device (e.g., between terminals 3 and 4, and 5 and 6 of a safety interlock switch) in both states.
- 3
Check resistance of individual wire runs from the safety device output terminals to the safety controller input terminals (e.g., from safety switch 3 to controller MonIn_CH1).
- 4
Increase the discrepancy time parameter (e.g., P_MON_DISCREPANCY_DELAY_G1) in the safety controller configuration if inputs are switching asynchronously but within acceptable limits.
- 5
Verify that the monitored device (e.g., safety light curtain OSSD outputs) has stable power supply and is not experiencing internal faults.