Übersetzen...
16

Short circuit

Danfoss · VLT HVAC Drive FC 102

Was bedeutet 16 ?

A direct short circuit exists in the motor windings or the motor wiring connected to the frequency converter's output terminals. This is a critical fault that can cause immediate and severe damage to the frequency converter's output stage if power is not removed quickly. Continued operation is highly dangerous.

Häufige Ursachen

  • Direct short circuit between two or more motor phases (U-V, V-W, U-W) within the motor windings.
  • Direct short circuit between two or more conductors in the motor output cable due to insulation damage or faulty termination.
  • Insulation failure within the motor allowing a direct phase-to-phase short.
  • Water or conductive debris ingress into the motor terminal box causing a short circuit between phases.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Disconnect the motor cables from the drive's output terminals (U, V, W).

  2. 2

    Measure the resistance between each pair of motor output terminals (U-V, V-W, U-W) at the drive's output side of the cable; readings should be balanced and non-zero (not 0 Ohms).

  3. 3

    Perform an insulation resistance test (Megger) between each motor phase to ground and between phases at the motor terminal box to detect insulation breakdown.

  4. 4

    Visually inspect the motor connection box and cable terminations for signs of arcing, carbon tracking, or conductive foreign material.

Alle Codes in diesem Handbuch durchsuchen (75)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes