Übersetzen...
17

Control Word Timeout

Danfoss · VLT HVAC Drive FC 102

Was bedeutet 17 ?

The drive has not received a valid control word from the external controller (e.g., PLC via fieldbus) within the expected timeframe. This indicates a communication failure, causing the drive to stop or trip for safety reasons.

Häufige Ursachen

  • Interruption or failure of the fieldbus communication link (e.g., disconnected cable, network switch fault).
  • The fieldbus master controller (e.g., PLC) has stopped sending a valid control word within the configured timeout period.
  • Incorrect fieldbus configuration parameters in the drive (e.g., P8-01, Fieldbus Address; P8-02, Baud Rate) or in the master.
  • Drive parameter P8-10 (Control Word Timeout) is set to a value that is too short for the network latency or PLC cycle time.
  • Faulty fieldbus option card in the drive preventing reception or processing of control words.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Inspect the fieldbus communication cable (e.g., Ethernet, Profibus) for physical damage, loose connections, or incorrect shielding at both the drive and the master controller.

  2. 2

    2. Verify the operational status of the fieldbus master (e.g., PLC), checking its diagnostic LEDs and internal diagnostic buffer for communication errors.

  3. 3

    3. Confirm that all fieldbus parameters in the drive (e.g., P8-01, Fieldbus Address; P8-02, Baud Rate) precisely match the settings in the master controller.

  4. 4

    4. Monitor the drive's fieldbus status (e.g., P8-03, Fieldbus Status Word) and confirm that control words are being received consistently from the master.

  5. 5

    5. Increase the drive parameter P8-10 (Control Word Timeout) to a longer duration (e.g., 5-10 seconds) if transient network delays are suspected, after confirming network stability.

Alle Codes in diesem Handbuch durchsuchen (75)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes