36

Mains failure

Danfoss · VLT HVAC Drive FC 102

Was bedeutet 36 ?

The frequency converter has detected a loss of incoming supply voltage, and the 'Mains Failure' parameter (14-10) is configured to generate an alarm. This indicates a power supply interruption to the drive, which will cause the motor to stop. Until mains power is restored, the drive cannot operate.

Häufige Ursachen

  • Total loss of incoming three-phase (L1, L2, L3) or single-phase supply voltage to the drive.
  • Blown fuse or tripped circuit breaker in the upstream power distribution system feeding the drive.
  • Loose or corroded connection at the main power input terminals (e.g., L1, L2, L3) of the drive.
  • Parameter 14-10 (Mains Failure) is set to 'Trip' instead of 'No function' or 'Freeze output' during intended voltage dips.
  • Severe voltage imbalance or sag on one or more phases causing the drive's input monitoring to trigger.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Check all upstream fuses and circuit breakers in the main power distribution panel.

  2. 2

    2. Measure the incoming line-to-line and line-to-neutral voltages at the drive's L1, L2, L3 input terminals.

  3. 3

    3. Verify the setting of parameter 14-10 (Mains Failure Function) to ensure it aligns with operational requirements.

  4. 4

    4. Inspect all main power wiring connections at the drive for tightness, corrosion, or signs of overheating.