Übersetzen...
38.1316

Internal Fault: Option software in slot B not supported

Danfoss · VLT HVAC Drive FC 102

Was bedeutet 38.1316 ?

The software on the option card installed in slot B is not recognized or supported by the frequency converter's firmware. This indicates a fundamental incompatibility, preventing the option card from integrating correctly with the drive's control system.

Häufige Ursachen

  • Installation of an option card in slot B with unsupported or incompatible software (e.g., beta firmware, custom modification).
  • The drive's main firmware version is too old to recognize or interface with the software on the installed option card.
  • Corruption of the option card's firmware, rendering it unreadable or unrecognizable by the main drive.
  • Attempting to use an option card from a different product series or manufacturer that is physically installed but logically incompatible.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    1. Record the exact model number and part number of the option card installed in slot B.

  2. 2

    2. Verify the frequency converter's main firmware version via the LCP (parameter 15-00) or manufacturer software.

  3. 3

    3. Refer to the manufacturer's compatibility matrix or documentation to confirm that the option card's software is officially supported by the drive's current firmware version.

  4. 4

    4. If compatibility is confirmed, attempt to re-flash the option card's firmware with the latest officially supported version using manufacturer software.

  5. 5

    5. If incompatibility is identified, replace the option card in slot B with a supported model, or update the main drive firmware if the option card is newer and requires it for compatibility.

Alle Codes in diesem Handbuch durchsuchen (75)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Danfoss 38.1316 — Behebung: Internal Fault: Option software… | ErrorLib