10033

Velocity Control Cycle Mismatch

Fanuc · Alpha i Series Servo Amplifier

Was bedeutet 10033 ?

This invalid parameter setting alarm occurs when the ITP (Interpolation Time Period) cycle is 16 ms, but an incorrect 500 μs is selected as the velocity control cycle. For this ITP cycle, the velocity control cycle must be 2 ms.

Häufige Ursachen

  • The sampling cycles for velocity control are not synchronized.
  • Discrepancy in the timing of feedback loops within the velocity control system.
  • A communication delay is causing the control loop cycle to mismatch.
  • Parameter P510.1 (Control Cycle Time) is misconfigured.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Correct the parameter related to interrupt cycle setting to ensure the velocity control cycle is 2 ms when the ITP cycle is 16 ms.