Alarm 5

System Alarm: Feedback Mismatch, Semi-Closed Loop Error, or Current Offset Error

Fanuc · Alpha i Series Servo Amplifier

Was bedeutet Alarm 5 ?

This alarm can indicate multiple issues depending on the set bits. If the OFS bit is set, it is a Feedback Mismatch alarm, suggesting opposite move directions for the position and velocity detectors. Other bits include MCC for Excessive Semi-Closed Loop Error and LDM for Current Offset Error.

Häufige Ursachen

  • Discrepancy between commanded position and actual feedback position.
  • Error detected in a semi-closed loop configuration.
  • The current offset of the motor is outside acceptable limits.
  • Feedback signal from the encoder or sensor is unreliable.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    If the OFS bit is set (Feedback mismatch alarm), check the rotation direction of the separate detector.

  2. 2

    If the separate detector's direction is opposite to the motor's rotation: For a Phase A/B detector, reverse the A and __A connections.

  3. 3

    If the separate detector's direction is opposite to the motor's rotation: For a Serial detector, reverse the signal direction setting for the separate detector.

  4. 4

    For Series 90B0/07 and subsequent editions, verify the setting that allows the signal direction to be reversed even for the phase A/B detector.