Übersetzen...
SV0477

ILLEGAL MACHINE POS.(SV)

Fanuc · Alpha i Series Servo Amplifier

Was bedeutet SV0477 ?

The servo detected that the machine position on the axis is not within the safety area (parameter No.13831 to 13838) during safety monitoring (when the safety check request signal (*VLDVx) is 0). This indicates the axis moved outside its defined safe operating envelope after the machine reference position was established, which can lead to collisions or unsafe conditions.

Häufige Ursachen

  • Machine reached an unexpected position due to external forces or incorrect command.
  • Axis limit switch triggered unexpectedly during movement.
  • Following error too large, exceeding P1-54.
  • Incorrect homing sequence or lost position reference.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Confirm that parameters No.13831 to 13838 define the correct safety area for the machine.

  2. 2

    Verify that the axis operation program ensures movement is performed within the established safety area.

  3. 3

    Ensure the machine reference position has been correctly established for the affected axis.

Alle Codes in diesem Handbuch durchsuchen (101)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Fanuc Alpha i Series Servo Amplifier