102

AC voltage too high

Fronius · Primo GEN24

Was bedeutet 102 ?

The AC grid voltage at the inverter's connection point is too high, exceeding the permitted limits for the Fronius Primo GEN24 208-240 inverter. This condition can lead to the inverter disconnecting from the grid to protect itself and the system.

Häufige Ursachen

  • The grid voltage is too high.
  • Impedance in the AC connection cable is too high (cable too long, cross-section too small).
  • The grid impedance is too high (local grid problem).

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Verify the AC grid voltage at the inverter's connection point using a multimeter and compare it with the Fronius Primo GEN24 208-240 inverter's specified operating limits.

  2. 2

    Check the length and cross-section of the AC connection cable; ensure it is adequately sized for the distance and current to minimize impedance.

  3. 3

    Inspect all AC connections for proper termination and secure contact.

  4. 4

    Contact the grid operator to report excessively high grid voltage or high grid impedance issues in the local network.

  5. 5

    If applicable, check inverter settings related to grid voltage limits to ensure they comply with local grid codes.