WSD Open
Fronius · Primo GEN24
Was bedeutet 1030 ?
This status code, indicated by a flashing red operating LED on the Fronius Primo GEN24 inverter, signifies that a device within the Wired Shutdown (WSD) chain has interrupted the signal line. This can occur if a surge protection device (SPD) has tripped, the factory-installed bypass has been removed, or a trigger device is not properly installed.
Häufige Ursachen
- A device connected in the WSD chain (e.g., surge protection device) has interrupted the signal line.
- The bypass device pre-installed at the factory has been removed.
- No trigger device has been installed in the WSD chain.
- The SPD surge protection device has tripped, causing the signal interruption.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
If an SPD surge protection device has tripped, the inverter must be repaired by an authorized specialist.
- 2
Install the bypass device that was originally installed ex works, or install a new trigger device into the WSD chain.
- 3
Turn the WSD (wired shutdown) switch to position 1 to configure the inverter as the WSD primary device.
- 4
Ensure all installation and connection of an SPD surge protection device is carried out by Fronius-trained service personnel, strictly adhering to technical specifications and safety rules.