Übersetzen...
30

Program Lost

Indramat · ServoDyn D Servo Drive

Was bedeutet 30 ?

This error occurs when the CLM01.3-M's back-up battery, which stores the user program when power is off, is disconnected or has low voltage. This leads to the loss of the application program, requiring re-entry or restoration.

Häufige Ursachen

  • The lithium back-up battery (on the MOK 11 card) is disconnected, depleted, or has low voltage.
  • The user program was not re-entered or restored after a battery replacement or power loss.
  • The MOK 11 card (Memory and Battery Module) is faulty or improperly seated.
  • Firmware replacement or update without proper program backup/restore procedure.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Turn OFF power to the CLM01.3-M.

  2. 2

    Remove the MOK 11 card (Memory and Battery Module) as shown in Figure 2.3 of the manual.

  3. 3

    Replace the 3.6-volt lithium back-up battery on the MOK 11 card.

  4. 4

    After replacing the battery, turn power ON and reload the user program into the CLM01.3-M (refer to Chapter 5).

  5. 5

    Verify that all CLM01.3-M program blocks are correctly entered and functional after restoration.

Alle Codes in diesem Handbuch durchsuchen (51)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes

Quelle: Indramat ServoDyn D Servo Drive