RS Para # Too Big
Indramat · ServoDyn D Servo Drive
Was bedeutet RS 07 ?
This serial communication error is a specific instance of "RS Para # Wrong", indicating that the parameter number transmitted to the CLM01.3-M is greater than 99. The CLM01.3-M expects parameter numbers to be in the range of 00 to 99.
Häufige Ursachen
- The parameter number in the serial command is greater than 99.
- Typographical error in the parameter number during transmission, e.g., an accidental extra digit.
- Sending device software error, attempting to access a non-existent parameter number.
- Using an incorrect parameter list for the CLM01.3-M, leading to attempts to access out-of-range parameters.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify that the parameter number being transmitted is between 00 and 99. Refer to Chapter 7 (Serial Interface) for the correct parameter format.
- 2
Correct the parameter number in the transmitted serial command to be within the valid range.
- 3
Check the serial communication link for data corruption or unusual characters.
- 4
Re-transmit the parameter command after verifying the parameter number.
- 5
Ensure the sending device's software uses the correct parameter map for the CLM01.3-M.