26105
Ground fault, KPP/KSP (axis)
Kuka · KR C4 extended
Was bedeutet 26105 ?
This fault indicates an overcurrent condition within the power unit, specifically identified as a ground fault. This means there is an unintended current path to ground, often through compromised insulation. This poses a risk of electrical shock, equipment damage, and system shutdown.
Häufige Ursachen
- Insulation breakdown in the motor cable.
- Internal motor winding insulation breakdown causing a short to ground.
- Faulty KSP (Kinematic Sensor Package) component.
- Faulty KPP (Kinematic Power Package) component.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check motor cable for damage to insulation.
- 2
Check motor windings for insulation breakdown to ground (e.g., using a megger).
- 3
Reinitialize the drive bus: Power Off / Power On.
- 4
Check KSP module for faults.
- 5
Check KPP module for faults.
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026