26108

Intermediate circuit voltage too low, KPP/KSP (axis)

Kuka · KR C4 extended

Was bedeutet 26108 ?

This fault indicates an undervoltage condition in the intermediate DC link circuit during operation. This usually points to issues with the incoming power supply or the drive's charging circuit. Persistent undervoltage can lead to unreliable drive operation and potential damage if the drive attempts to operate outside its specified voltage range.

Häufige Ursachen

  • Mains voltage dropping below the permissible input range for the drive.
  • Faulty intermediate circuit cabling.
  • Malfunction in the KPP/KSP charging circuit.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Check trace recording of the intermediate circuit voltage.

  2. 2

    Check mains voltage at the input to the drive.

  3. 3

    Check intermediate circuit cabling for loose connections or damage.

  4. 4

    Reinitialize the drive bus: Power Off / Power On.

  5. 5

    Check KSP module for faults.

  6. 6

    Check KPP module for faults.