Starting Frequency Exceeds Jogging Frequency
Omron · MX2 Inverter
Was bedeutet 037 ?
This warning indicates that the inverter's starting frequency (b082) is set higher than the jogging frequency (A038). This inconsistency can cause an abrupt speed change when transitioning from a jog command or if jogging is initiated at startup, potentially leading to jerky motion or mechanical stress.
Häufige Ursachen
- b082 (Starting Frequency) was manually configured to a value exceeding A038 (Jogging Frequency).
- A038 (Jogging Frequency) was inadvertently lowered to a value below the configured b082.
- An inconsistent parameter setup where the drive attempts to start at a frequency higher than its defined jog speed.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Access parameters b082 (Starting Frequency) and A038 (Jogging Frequency). Compare their values.
- 2
Adjust b082 (Starting Frequency) to be less than or equal to A038 (Jogging Frequency).
- 3
Alternatively, if the application requires b082 to be higher for normal starts, increase A038 (Jogging Frequency) to be equal to or greater than b082.
- 4
Save the parameter changes and power cycle the drive to confirm the settings are active.
- 5
Initiate a jog command and observe the drive's behavior to ensure a smooth transition and correct jog speed.