924
FIELD CURRENT SETTING FAULT
Otis · DSD 412 Elevator System
Was bedeutet 924 ?
This fault is declared if a number entered for Rated Field Current #50 is outside the acceptable range of the Field Interface board, A3, current rating. This rating is determined by the field sense resistor selected by SW1 on the Field Interface PCB. This fault requires a DSD power down.
Häufige Ursachen
- Rated Field Current parameter #50 set outside the acceptable range of the Field Interface board, A3, current rating.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Enter a valid number for Rated Field Current, #50, within the acceptable range determined by the Field Interface board, A3, current rating and SW1 selection.