932

Armature CEMF volts >20% of rated during test.

Otis · DSD 412 Elevator System

Was bedeutet 932 ?

This fault indicates that the Armature CEMF voltage exceeds 20% of its rated value during a test. This condition may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).

Häufige Ursachen

  • Motor is rotating during the test, producing CEMF.
  • High motor armature resistance.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Ensure the motor is mechanically locked and not rotating during the test.

  2. 2

    Ensure that the brush commutator is clean to minimize armature resistance.

  3. 3

    Temporarily increase parameter #7 (Rated Armature Volts) during the test.

Alle Codes in diesem Handbuch durchsuchen (57)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026