933
Motor armature current does not increase to near test amps within 6 seconds.
Otis · DSD 412 Elevator System
Was bedeutet 933 ?
This fault indicates that the motor armature current failed to reach near the specified test amperes within 6 seconds. This may occur during Self-Tune (Function #997) or Self-Diagnostic (Function #998).
Häufige Ursachen
- Faulty motor armature circuit, possibly an open circuit.
- Open SCR or missing SCR gating pulses.
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Check the motor armature circuit wiring for any open circuits.
- 2
Inspect the motor itself for any internal open circuits.
- 3
Perform Self-Diagnostics (Function #998) to verify the status of SCRs and their gating.