Übersetzen...
>LS-FAULT !

1LS / 2LS Check Negative

Otis · GAA21750AK3 Service Tool

Was bedeutet >LS-FAULT ! ?

This blinking event message indicates that the safety check for Limit Switch 1 (1LS) or Limit Switch 2 (2LS) has failed, blocking elevator operation. This fault implies a critical issue with the limit switch integrity or its monitoring circuit on the OTIS 2000 Controllers MCS120/MCS220.

Häufige Ursachen

  • Malfunction of Limit Switch 1 (1LS) or Limit Switch 2 (2LS).
  • Incorrect wiring or poor connection to 1LS or 2LS.
  • Mechanical damage or misalignment of the limit switches.
  • Fault in the LCB_II control system's monitoring of limit switches.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect Limit Switch 1 (1LS) and Limit Switch 2 (2LS) for physical damage, obstruction, or misalignment.

  2. 2

    Verify electrical connections to both 1LS and 2LS for continuity and proper termination.

  3. 3

    Measure the voltage across the 1LS and 2LS terminals in both actuated and non-actuated states, comparing with expected values.

  4. 4

    If accessible, manually actuate each limit switch to confirm its switching action.

Alle Codes in diesem Handbuch durchsuchen (15)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes