Übersetzen...
LFF

4-20 mA loss

Schindler · Altivar 312 Drive

Was bedeutet LFF ?

This fault indicates a loss of the 4-20 mA analog input signal, which is typically used for speed reference or process feedback. This can occur even if the [4-20mA loss] (LFL) parameter is set to [No] (nO) on page 95.

Häufige Ursachen

  • Disconnection or break in the 4-20 mA analog input wiring.
  • Malfunction of the device providing the 4-20 mA signal.
  • Incorrect wiring or configuration of the 4-20 mA input.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Measure the 4-20 mA signal directly at the drive's analog input terminals.

  2. 2

    Check the wiring for the 4-20 mA analog input for continuity and correct connections.

  3. 3

    Verify the settings of the analog input parameters.

Alle Codes in diesem Handbuch durchsuchen (32)
Verifizierte technische Daten. Zuletzt aktualisiert: March 2026

Verwandte Fehlercodes