Frequency converter overtemperature
Vacon · NXP/C
Was bedeutet 14 ?
The heatsink temperature of the frequency converter has exceeded 90 °C (a warning is issued at 85 °C). Subcodes in T.14 indicate the measurement source (S1 = Measurement, S2 = Internal thermistor). Prolonged operation at high temperatures can cause irreversible damage to the drive's internal components.
Häufige Ursachen
- Overheating of the converter heatsink.
- Ambient temperature too high.
- Cooling fan failure or malfunction.
- Blocked ventilation grilles or dust accumulation.
- Excessive switching frequency or high load operation (P1-06).
Reparaturschritte & Checkliste
Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.
- 1
Verify that the cooling fan(s) of the frequency converter are operating correctly and providing adequate airflow.
- 2
Clean any dust or debris from the heatsink fins to ensure efficient heat dissipation.
- 3
Measure the ambient temperature surrounding the frequency converter; ensure it is within the specified operating limits.
- 4
Review parameter settings for switching frequency; reduce it if found to be too high in relation to the ambient temperature and motor load.