17

Motor underload

Vacon · NXP/C

Was bedeutet 17 ?

The motor underload protection has tripped, indicating that the motor is operating with significantly less load than expected or specified. This can be due to a disconnected load, broken component in the mechanical system, or incorrect parameter settings.

Häufige Ursachen

  • Motor current consistently below expected minimum.
  • Low load or no load conditions (P1-08 < P1-09).
  • Motor not connected properly.
  • Faulty motor or winding.
  • Incorrect current sensing parameters.

Reparaturschritte & Checkliste

Klicken Sie auf Schritte, um Ihren Fortschritt zu verfolgen.

  1. 1

    Inspect the mechanical load connected to the motor for any disengagement, breakage, or abnormal reduction.

  2. 2

    Verify that the process being driven by the motor is functioning correctly and demanding the expected load.

  3. 3

    Review the motor underload protection parameters (e.g., minimum current threshold, delay time) in the frequency converter to ensure they are set appropriately for the application.