Earth Fault / Output Current Unbalance
ABB · ACS560 Standard Control Program Firmware
What does 2330 mean?
The drive has detected a load unbalance, typically due to an earth fault in the motor or motor cable, or excessive output current unbalance in an inverter unit (for parallel connected modules). This condition poses a significant electrical safety risk, can lead to equipment damage, insulation breakdown, or fire, and indicates an internal fault if external causes are ruled out.
Common Causes
- Insulation breakdown between a motor phase winding and the motor frame, causing current to flow to earth (ground).
- Damage to the motor cable insulation (e.g., cuts, abrasions, moisture ingress) causing a short circuit to the cable shield or ground.
- Water or conductive dust ingress into the motor terminal box or the motor windings, creating a path to earth.
- Internal short circuit or failure within the drive's output inverter stage, leading to unbalanced phase currents.
- Faulty current sensor (Hall effect sensor) on one of the drive's output phases, providing an incorrect reading.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Disconnect the motor cables from the drive, then measure insulation resistance of each motor phase to ground (PE) at the motor terminal box using a megohmmeter (e.g., 500VDC test voltage).
- 2
2. Measure insulation resistance of each motor cable phase conductor to its shield (or conduit) using a megohmmeter (e.g., 500VDC test voltage).
- 3
3. Visually inspect the motor terminal box for signs of moisture, contamination, or loose connections to the motor phases.
- 4
4. With motor cables disconnected, reset the drive and measure the output current (P1-16 or individual phase currents) from the drive to verify balance without load.
- 5
5. Inspect the motor cable for any visible signs of damage, pinching, or wear along its entire length.