3220

DC UNDERVOLT

ABB · ACS560 Standard Control Program Firmware

What does 3220 mean?

The intermediate circuit DC voltage is insufficient, typically due to a missing supply voltage phase, a blown input fuse, or an internal rectifier bridge fault. This condition prevents the drive from powering the motor correctly, leading to a shutdown or inability to start.

Common Causes

  • Loss of one or more phases (L1, L2, L3) of the incoming AC supply voltage to the drive.
  • Blown input fuses (e.g., F1, F2, F3) or tripped input circuit breaker (e.g., Q1) on the supply side of the drive.
  • Insufficient incoming AC supply voltage (e.g., below 340V for 400V drives) due to sag or overloaded supply transformer.
  • Failure of one or more diodes in the drive's internal rectifier bridge.
  • Loose or corroded power connections at the drive's input terminals or supply contactor.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Measure the incoming AC line voltages (L1-L2, L2-L3, L3-L1) at the drive's input terminals and verify all phases are present and at nominal voltage.

  2. 2

    2. De-energize and lock out power, then measure continuity of all input fuses or verify state of input circuit breaker.

  3. 3

    3. Measure the DC bus voltage at the drive's intermediate circuit terminals (DC+, DC-) and compare it against the expected voltage (e.g., ~560VDC for 400VAC input).

  4. 4

    4. With power isolated, perform a diode check on the drive's internal rectifier bridge using a multimeter in diode mode.

  5. 5

    5. Check all power wiring connections at the drive's input terminals, supply contactor, and main disconnect for tightness and proper seating.

Browse all codes in this manual (33)
Verified technical data. Last updated: April 2026