ABB · ACS560 Standard Control Program Firmware
The measured temperature of motor 2 has exceeded the alarm limit defined by parameter 35.05. This indicates a potential overheating situation specific to this motor, which can lead to insulation degradation and reduced motor lifespan if not addressed.
Click steps to track your progress.
1. Measure the actual winding temperature of Motor 2 using an external temperature probe and compare it to the alarm limit (P35-05).
2. Monitor Motor 2's operating current (P1-15 if configured for M2) and compare it against its rated current, reducing the mechanical load if necessary.
3. Inspect Motor 2's cooling fan for proper operation and clean any dust or debris from its cooling fins.
4. Verify the integrity and calibration of the temperature sensor connected to Motor 2 by measuring its resistance at known temperatures.
5. Check parameter P35-05 (Motor 2 Temperature Alarm Limit) and adjust it to a value consistent with the motor's insulation class if necessary.