7302

Encoder Phase A/B Swap

ABB · ACS560 Standard Control Program Firmware

What does 7302 mean?

The pulse encoder phasing is incorrect, specifically Phase A is connected to the terminal for Phase B and vice versa. This wiring error will cause the drive to misinterpret motor direction and speed, leading to incorrect motor operation, instability, or immediate trips.

Common Causes

  • Encoder A and B phase signal wires (e.g., terminals X1, X2) are physically swapped at the drive's encoder input terminal block.
  • Encoder A and B phase signal wires are physically swapped at the encoder's connector or terminal box.
  • Incorrect wiring drawing followed during initial installation, leading to the A/B swap.
  • Drive parameter (e.g., P3-02) for encoder direction or phase order is incorrectly configured, reversing the expected logic.
  • Damaged encoder input circuit on the drive's control board, misinterpreting the phase order.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. De-energize and lock out power, then physically swap the encoder A and B phase wires (e.g., terminals X1 and X2) at the drive's encoder input terminals.

  2. 2

    2. Alternatively, if physical swap is difficult, check if a parameter (e.g., P3-02) exists in the drive to electronically reverse encoder direction or phase order.

  3. 3

    3. Verify the wiring diagram for the specific encoder and drive model to confirm correct A and B phase connections.

  4. 4

    4. Rotate the motor manually and observe the drive's reported speed and direction feedback (e.g., P3-03) after correcting the phase order.

  5. 5

    5. Check for correct connection of the complementary signals (A_not, B_not) as swapping these without swapping A and B will also cause issues.

Browse all codes in this manual (33)