ABB · ACS560 Standard Control Program Firmware
The inverter type (e.g., sr0025_3) has been changed, typically at the factory or during drive implementation. This fault indicates that the new configuration needs to be validated before the drive can operate correctly, requiring a specific power-off sequence.
Click steps to track your progress.
Confirm the model and firmware version of the installed control board and power module match the original specification.
Perform a factory reset (e.g., P99-01 = 1) and then re-enter or reload parameters from a known good backup file.
Verify all installed option cards (e.g., fieldbus module, I/O extension) are compatible with the drive model and firmware.
Attempt to re-upload the correct firmware using the manufacturer's commissioning tool, ensuring checksum validation passes.
If available, try swapping the control board with a known good, compatible spare, then attempt to power cycle the drive.