ABB · ACS560 Standard Control Program Firmware
A fault has occurred on the line-side converter of the drive system. This indicates a problem with the input power stage that converts AC supply to DC bus voltage, potentially affecting the drive's ability to operate or drawing excessive current.
Click steps to track your progress.
1. De-energize and lock out power, then measure continuity of each input phase fuse using a multimeter.
2. Measure the input AC voltage (L1-L2, L2-L3, L3-L1) at the drive's input terminals and compare to nominal supply voltage.
3. With power isolated, perform a diode check on the input rectifier bridge (or IGBTs) using a multimeter in diode mode, comparing values for each phase.
4. Inspect the DC link capacitors for physical signs of damage (e.g., bulging, leakage) and measure their capacitance if possible.
5. Verify the integrity of control wiring and connections to the gate driver board for the line-side converter.