ABB · ACS560 Standard Control Program Firmware
The output filter choke of the drive is experiencing excessive temperature. This supervision is active in step-up drives and points to inadequate cooling or excessive current through the choke, which can lead to overheating and potential damage to the filter components, impacting drive output quality.
Click steps to track your progress.
Inspect the output filter choke for dust accumulation or debris blocking cooling fins. Clean any obstructions.
Verify the operation of any dedicated cooling fans for the output filter choke by checking for airflow and fan rotation.
Monitor the actual motor current (e.g., r0027) during operation to ensure it does not consistently exceed the choke's current rating.
Measure the ambient temperature within the control cabinet near the choke; ensure it is within the specified operating range (e.g., <40°C).
Check for correct motor parameters (e.g., P03-01 to P03-08) configured in the drive, as incorrect values can lead to improper motor control and choke stress.