ABB · ACS560 Standard Control Program Firmware
An overtemperature condition has been detected on the AINT board of an inverter module. Prolonged operation at elevated temperatures can lead to accelerated degradation and eventual failure of critical electronic components on the board.
Click steps to track your progress.
1. Verify the proper operation of the inverter module's internal cooling fan(s) by checking for rotation and airflow.
2. Measure the ambient temperature inside the electrical cabinet using a thermometer and compare it to the drive's specified operating range.
3. Inspect all cooling air inlets and outlets on the drive and cabinet for obstructions, dust filters for clogging, and clean as necessary.
4. Check parameter P1-10 (Overload trip level) and actual motor current (P1-15) to determine if the drive is operating at or above its continuous rating.
5. Ensure proper sealing of the cabinet (if applicable) and check for any external heat sources contributing to elevated internal temperatures.