Overtemperature has occurred in the choke of a liquid-cooled R8i inverter module. Excessive heat in the choke can reduce its magnetic properties and potentially lead to insulation breakdown, compromising drive performance and safety.
Click steps to track your progress.
1. Verify the cooling liquid flow rate (e.g., liters/minute) to the R8i module and compare it to the drive's specified minimum flow.
2. Measure the temperature of the cooling liquid entering and exiting the R8i module's cooling circuit, checking for expected differential.
3. Inspect the cooling liquid filters for clogging and clean or replace as required, then check for pump operation.
4. Monitor the motor current (P1-15) and drive output current (P1-16) to ensure they are within the choke's continuous current rating.
5. Measure the resistance of the choke temperature sensor and compare it to the sensor's temperature-resistance curve to confirm accuracy.