ABB · ACS560 Standard Control Program Firmware
A source selection (pointer) parameter has been configured to point to a non-existent parameter index. This indicates a configuration error in the drive's settings, which can lead to incorrect parameter referencing and potentially erratic or undefined drive behavior.
Click steps to track your progress.
Identify the specific pointer parameter (e.g., P5-01) causing the error from the drive's fault log or diagnostic screen.
Access the identified pointer parameter (e.g., P5-01) and verify its configured value, which represents the target parameter index.
Cross-reference the target parameter index (e.g., 3099) with the drive's current parameter manual to confirm its existence and validity for the installed firmware.
If the target parameter index is invalid, reset the pointer parameter (e.g., P5-01) to a known valid index (e.g., 0 for no selection) or a valid, existing parameter (e.g., P3-01 for Analog Input 1).
If the parameter set was loaded from a backup, verify the drive model and firmware version of the source backup match the current drive's specifications (e.g., displayed via P0-03).
Perform a factory reset of the drive (e.g., using parameter P0-99 set to 1) and meticulously reconfigure essential parameters, paying close attention to all pointer parameter settings.