ABB · ACS580
An earth (ground) fault or significant current unbalance has been detected in the motor circuit, specifically within the motor itself or its connecting cables. This is a critical safety hazard and can cause severe damage to equipment or pose a risk of electric shock.
Click steps to track your progress.
De-energize the drive. Disconnect the motor cable from the drive output terminals (U, V, W, PE).
Measure insulation resistance of each motor cable conductor to ground (PE) and between conductors using a megohmmeter (1000V).
Measure insulation resistance of each motor winding to ground (motor frame) and between phases using a megohmmeter (1000V).
Visually inspect the motor terminal box, motor cable glands, and cable routing for signs of moisture, damage, or contamination.
Verify the integrity of the motor frame grounding connection to the central earthing point.