ABB · ACS850 Standard Program Firmware
This fault indicates a loss of Process Data Object (PDO) communication between a remote axis (Client Node, CN) and the manager (Master Node, MN), specifically when at least two consecutive PDO packets are not received. For a NextMove e100, it means a drive has disappeared from the network. Unresolved, this can lead to loss of control over the remote axis and system instability.
Click steps to track your progress.
1. Inspect the EtherCAT cable between the Master Node and Client Node for physical damage, ensuring secure connections at both RJ45 ports.
2. Verify the EtherCAT cable shield is properly terminated at the master and slave devices to mitigate EMI.
3. Check the Master Node's configuration file for correct PDO mapping and update rates for the Client Node.
4. Monitor the network status LEDs on both the Master and Client Node (e.g., EtherCAT Link/Activity LEDs) for link integrity.
5. Review the Master Node's diagnostic log for specific communication errors related to the Client Node ID.
6. Temporarily reduce the EtherCAT Master's cycle time or increase the watchdog timeout period (if configurable) to test for timing issues.