ABB · ACS850 Standard Program Firmware
This information message indicates that the battery backup supply for a Smart Absolute (Smart Abs) encoder has failed. This typically appears during startup or when the drive is enabled. A dead encoder battery means the absolute position information will be lost during power cycles, requiring re-homing or potentially causing incorrect startup positions.
Click steps to track your progress.
Obtain a replacement battery for the specific Smart Absolute encoder model as recommended by the manufacturer.
Power down the drive and machine, then carefully open the encoder's battery compartment (if external) or replace the entire encoder unit if the battery is internal.
Install the new battery, ensuring correct polarity (e.g., + and - terminals).
Power up the drive and verify that the "Encoder battery dead" message is no longer present in the error log (e.g., S6-01 (Encoder Status) indicates healthy).
If absolute position was lost due to the dead battery, perform an absolute position homing routine (e.g., HOME command, P5-01 (Homing Mode)) to re-establish the machine's reference.