This is a general EtherCAT Application Layer (AL) status code, indicating that the EtherCAT master received an error code from the drive. The specific fault is detailed by an associated Profile Code in the Mint WorkBench Error Log, which needs to be converted to hexadecimal for interpretation. Without resolving the underlying EtherCAT error, the drive will not communicate correctly, preventing coordinated motion.
Click steps to track your progress.
1. Retrieve the specific EtherCAT Profile Code from the Mint WorkBench Error Log or the EtherCAT Master's diagnostic interface.
2. Consult the EtherCAT slave device's documentation for the retrieved Profile Code to understand the specific AL error.
3. Verify the EtherCAT Master's configuration (ENI file) against the slave device's ESI file for compatibility.
4. Check the EtherCAT network cabling and connection quality between the Master and the faulty slave device.
5. Power cycle the EtherCAT slave device and monitor its EtherCAT status LEDs during startup.
6. If the Profile Code indicates a parameter error, review relevant drive parameters (e.g., P8-01, P8-02) for correct EtherCAT settings.