ABB · ACS880
The drive's internal IGBT temperature has exceeded its safe operating limit, indicating potential overheating. This can lead to reduced lifespan or premature failure of the IGBTs if the root cause is not identified and resolved promptly.
Click steps to track your progress.
Allow the drive to cool down completely. Verify the ambient temperature in the control cabinet is within the drive's specification.
Check for proper operation of all internal cooling fans. Clean any dust or debris from the drive's heatsink fins and ventilation openings with compressed air.
Measure the output current (P7-01) and compare it to the drive's rated output current (from nameplate).
Verify motor parameters P1-01, P1-02, P1-03, and P1-04 (Motor Rated RPM) are correctly entered for the connected motor.
Ensure proper cabinet ventilation by checking filter mats, fan operation, and air circulation paths.