ABB · ACS880
An external temperature sensor (either 1 or 2) connected to the drive has registered a temperature beyond its configured fault limit. This indicates a potential overheating condition in the monitored equipment (e.g., motor), risking damage if not addressed.
Click steps to track your progress.
Measure the actual temperature of the monitored component (e.g., motor casing) using an infrared thermometer.
Verify the wiring of the external temperature sensor to the drive's input terminals (e.g., AI1/AI2) for continuity and insulation.
Check the drive parameter P5-10 (Ext. Temp. 1 Fault Limit) or P5-11 (Ext. Temp. 2 Fault Limit) against the sensor's specifications.
Measure the resistance or voltage output of the external sensor directly and compare to its characteristic curve for the measured temperature.
Confirm drive parameter P5-01 (Ext. Temp. 1 Type) or P5-02 (Ext. Temp. 2 Type) matches the physically installed sensor (e.g., PTC or Pt100).